Part no.: 77 8730 0000 30709-0185
M12 Female cable connector, Contacts: 2+7, moulded on the cable, IP67, PUR, black, Power: 2 x 0.75 (AWG 18), Signal: 7 x 0.14 (AWG 26), 1.85 m
M12-Hybrid, series 767, Automation Technology - Data Transmission
General features
MorelessPart no. | 77 8730 0000 30709-0185 |
Connector design | Female cable connector |
Cable length | 1.85 m (Other lengths are available on request.) |
Version | Connector socket straight |
Connector locking system | screw |
Termination | moulded on the cable |
Degree of protection | IP67 |
Cross-sectional area | Power: 0.75–1.5 mm², Signal: 0.14–0.25 mm² / Power: AWG 20-18, Signal: AWG 26-24 |
Temperature range from/to | -25 °C / 85 °C |
Mechanical operation | > 100 Mating cycles |
Weight (g) | 131.00 |
Customs tariff number | 85444290 |
Country of Origin | DE |
Electrical parameters
MorelessRated voltage | Power: 63 V, Signal: 12.5 V |
Rated impulse voltage | Power: 800 V, Signal: 500 V |
Rated current | 12 A Power / 0,5 A Signal |
Pollution degree | 2 |
Overvoltage category | II |
Insulating material group | I |
Material
MorelessHousing material | PUR |
Contact body material | TPU |
Contact material | CuSn (bronze) |
Contact plating | Au (gold) |
Locking material | Stainless steel |
REACH SVHC |
CAS 7439-92-1 (Lead) |
SCIP number | 667d0eb9-2eb5-4a44-94b0-ec902c875192 |
Classifications
MorelessETIM 9.0 | EC002638 |
Cable data
MorelessStructure of the cable | |
Cable diameter | 7.0 mm |
Cross section | Power: 2 x 0.75 (AWG 18), Signal: 7 x 0.14 (AWG 26) |
Sheath material | PUR |
Single-lead insulation | PP |
Single-lead structure | 2 x 0.75 mm² / 7 x 0.14 mm² |
Cable color | black |
Mechanical properties | |
Bending radius, fixed cable | 3 x Ø |
Bending radius, moving cable | 9 x Ø |
Thermal properties | |
Temperature range cable in move from/to | -20 °C / 60 °C |
Temperature range cable fixed from/to | -40 °C / 85 °C |
Security notices
- The connector must not be plugged or unplugged under load. Non-observance and improper use can result in personal injury.
- The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
- To protect against unintentional opening of the connector, the thread between the housing and the connector head must be secured with a suitable cyanoacrylate adhesive when used in circuits with voltages dangerous to the touch. This does not apply to connectors used in SELV and PELV circuits according to IEC 61140 (EN 61140, VDE 0140-1).
- Connectors which are used in circuits with voltages dangerous to the touch may only be installed and used by, or under the supervision of, persons with electrical engineering training, taking into account the applicable regulations and standards.
- The user must take suitable safety precautions to ensure that the connector cannot be accidentally disconnected.
- Plug connectors with enclosure protection IP67 and IP68 are not suitable for use under water. When used outdoors, the plug connectors must be protected separately against corrosion. For further information on the IP protection classes, please refer to the "Technical Information" download centre.
- The plug connector is not suitable for mains voltages Please observe the pollution degree and the overvoltage category. For further information, please refer to the download center "Technical Information".