Part no.: 79 5707 10 03
Connecting cable, Contacts: 2+2PE, unshielded, screw clamp, IP67, PUR, black, Circuit Z20, with LED PNP, 1 m
Size A, series 210, Automation Technology - Solenoid Valve Connectors
General features
MorelessPart no. | 79 5707 10 03 |
Connector design | Connecting cable |
Type standard | DIN EN 175301-803 |
Cable length | 1 m (Standard 1 m and 2 m. Other lengths are available on request.) |
Version | Connecting cable |
Connector locking system | Central bolt |
Termination | screw clamp |
Degree of protection | IP67 |
Cross-sectional area | 0.75 mm² / AWG 18 |
Temperature range from/to | -25 °C / 85 °C |
Mechanical operation | > 50 Mating cycles |
Additional information |
Circuit Z20 with LED PNP |
Weight (g) | 267.891 |
Customs tariff number | 85444290 |
Electrical parameters
MorelessRated voltage | 24 V |
Rated impulse voltage | 800 V |
Rated current | 4.0 A |
Insulation resistance | ≥ 1010 Ω |
Pollution degree | 3 |
Overvoltage category | II |
Insulating material group | II |
EMC compliance | unshielded |
Wiring | Z20 |
Material
MorelessHousing material | PC |
Contact body material | PA |
Contact material | CuSn (bronze) / CuZn (brass) |
Contact plating | Sn (tin) |
Classifications
MorelesseCl@ss 11.1 | 27-06-03-11 |
ETIM 9.0 | EC002638 |
Cable data
MorelessStructure of the cable | |
Cable diameter | 6.0 mm |
Sheath material | PUR |
Single-lead insulation | PVC |
Single-lead structure | 24 x 0.20 mm (Cu) |
Cable color | black |
Mechanical properties | |
Bending radius, fixed cable | 5 x Ø |
Bending radius, moving cable | 10 x Ø |
Thermal properties | |
Temperature range cable in move from/to | -5 °C / 70 °C |
Temperature range cable fixed from/to | -25 °C / 70 °C |
Other features | |
Halogen free | no |
Security notices
- The connector must not be plugged or unplugged under load. Non-observance and improper use can result in personal injury.
- The connectors have been developed for applications in plant engineering, control and electrical equipment construction. The user is responsible for checking whether the connectors can also be used in other areas of application.
- Connectors which are used in circuits with voltages dangerous to the touch may only be installed and used by, or under the supervision of, persons with electrical engineering training, taking into account the applicable regulations and standards.
- The user must take suitable safety precautions to ensure that the connector cannot be accidentally disconnected.
- Plug connectors with enclosure protection IP67 and IP68 are not suitable for use under water. When used outdoors, the plug connectors must be protected separately against corrosion. For further information on the IP protection classes, please refer to the "Technical Information" download centre.
- The plug connector is not suitable for mains voltages Please observe the pollution degree and the overvoltage category. For further information, please refer to the download center "Technical Information".